Detailed instructions for use are in the User's Guide.
[. . . ] AIR CONDITIONER (MULTI TYPE)
Installation manual
Outdoor Unit
Model name: <Heat Pump Model>
MMY-MAP0804HT8-E MMY-MAP1004HT8-E MMY-MAP1204HT8-E MMY-MAP1404HT8-E MMY-MAP1604HT8-E MMY-MAP0804HT8Z-E MMY-MAP1004HT8Z-E MMY-MAP1204HT8Z-E MMY-MAP1404HT8Z-E MMY-MAP1604HT8Z-E MMY-MAP0804HT8ZG-E MMY-MAP1004HT8ZG-E MMY-MAP1204HT8ZG-E MMY-MAP1404HT8ZG-E MMY-MAP1604HT8ZG-E
<Cooling Only Model>
MMY-MAP0804T8-E MMY-MAP1004T8-E MMY-MAP1204T8-E MMY-MAP1404T8-E MMY-MAP1604T8-E MMY-MAP0804T8Z-E MMY-MAP1004T8Z-E MMY-MAP1204T8Z-E MMY-MAP1404T8Z-E MMY-MAP1604T8Z-E MMY-MAP0804T8ZG-E MMY-MAP1004T8ZG-E MMY-MAP1204T8ZG-E MMY-MAP1404T8ZG-E MMY-MAP1604T8ZG-E
For commercial use Not accessible to the general public Vente interdite au grand public Kein öffentlicher Zugang Non accessibile a clienti generici No destinado al público en general Não acessível ao público em geral Niet geschikt voor huishoudelijk gebruik Genel eriime açik deildir
Installation manual
English
1-EN
1
SMMS-i Installation Manual SMMS-i Installation Manual
2-EN
Original instruction
ADOPTION OF NEW REFRIGERANT
This Air Conditioner uses R410A an environmentally friendly refrigerant.
Contents
1 PRECAUTIONS FOR SAFETY . This Installation Manual describes the installation method of the outdoor unit. For installation of indoor units, follow the Installation Manual supplied with the indoor unit. Moreover, as this installation manual includes the important articles concerning the "Machinery" Directive (Directive 2006/42/ EC), please read through the manual and make sure you understand it. [. . . ] When piping to outdoor units using Outdoor unit connection piping kits, intersect the pipes to the outdoor unit and those to indoor units at a right angle as shown in figure 1 on "6. INSTALLATION OF THE OUTDOOR UNIT".
· Be sure to apply pressure from the service ports of the packed valves (or ball valves) at the liquid side, gas side and balance pipe side. · An airtight test can only be performed at the service ports at the liquid side, gas side and balance pipe side on header unit. · Close the valves fully at the gas side, liquid side and balance pipe side. As there is a possibility that the nitrogen gas will enter into the cycle of outdoor units, re-tighten the valve rods at the liquid side and balance pipe side before applying pressure. (When using MAP140 or MAP160, you do not have to re-tighten the liquid side valve rod as their valves at the liquid side are ball valves. ) · For each refrigerant line, apply pressure gradually in steps at the liquid side, gas side and balance pipe side. Be sure to apply pressure at the gas side, liquid side, and balance pipe side.
WARNING
Never use oxygen, flammable gases, or noxious gases in an airtight test.
Allowable length and allowable height difference of refrigerant piping
Item
Total extension of pipe (liquid pipe, real length) Less than 96kW 96kW or more Less than 34HP or less 34HP or more Equivalent length Real length Equivalent length Real length
Allowable value
300m 500m 235m 190m 120m (*2) 100m (*2) 90m (*3) 25m 10m 30m 50m 70m (*4) 40m (*5) 40m 5m
Pipes
LA + LB + La + Lb + Lc + Ld + L1 + L2 + L3 + L4 + L5 + L6 + L7 + a + b + c + d + e + f + g + h + i + j LA + LB + Ld + L1 + L3 + L4 + L5 + L6 + j
Connected to indoor unit Main piping Gas side valve fully closed
Low pressure High pressure gauge gauge
Header outdoor unit Service port Brazed Copper pipe Fully closed
VL
VH Gauge manifold
Farthest piping length L (*1) Main piping length Pipe length
Packed valve details
L1 L3 + L4 + L5 + L6 + j LA + LB + Ld (LA + Lb, LA + LB + Lc) La, Lb, Lc, Ld a, b, c, d, e, f, g, h, i, j L2, L3, L4, L5, L6, L7 Balance service port To gauge manifold Liquid-side service port Liquid-side valve To outdoor unit To outdoor unit Gas-side valve
Reducing valve
Farthest equivalent piping length from the first branch Li (*1) Farthest equivalent piping length between outdoor units L0 (*1) Maximum equivalent piping length of pipes connected to outdoor units Maximum real length of pipes connected to indoor units Maximum equivalent length between branching sections Height between outdoor and indoor units H1 Height between indoor units H2 Height between indoor units H3 Upper outdoor units Lower outdoor units
To outdoor unit
Service port Gas-side service port Piping at site Liquid valve fully closed Fully closed
Copper pipe Nitrogen gas
Balance valve
Piping at site Piping at site
Service port Balanced pipe side valve fully closed
Height difference
Connected to other follower units
*1: *2: *3: *4: *5:
Farthest outdoor unit from the first branch: (D), farthest indoor unit: (j) If the total capacity of outdoor units is 46HP or more, make the equivalent length 70m (real length 50m) or less. Make the difference 65m or less if the height difference between outdoor and indoor units (H1) is more than 3m. Make the difference 50m or less if the height difference between indoor units (H2) is more than 3m. Make the difference 30m or less if the height difference between indoor units (H2) is more than 3m.
Able to detect a serious leakage 1. · If there is no pressure decrease after 24 hours, the test is passed.
EN
27-EN
14
28-EN
29-EN
15
SMMS-i Installation Manual SMMS-i Installation Manual
30-EN
NOTE
However, if the environmental temperature changes from the moment of applying pressure to 24 hours after that, the pressure will change by about 0. 01MPa (0. 1kg/cm²G) per 1°C. Consider the pressure change when checking the test result.
Vacuum drying
· Be sure to perform vacuuming from both liquid and gas sides. · Be sure to use a vacuum pump equipped with the counter-flow prevention function so that oil in the pump will not flow back into piping for air conditioners. (If oil in the vacuum pump enters in the air conditioner with R410A refrigerant, a problem may be caused in the refrigerating cycle. )
After finishing the airtight test and discharging nitrogen gas, connect the gauge manifold to the service ports of the liquid side, gas side, and balance pipe side and connect a vacuum pump as shown in the figure below. Be sure to perform vacuuming for the liquid, gas, and balance pipe sides.
Low pressure High pressure gauge gauge
REQUIREMENT
When pressure decrease is detected in steps 1-3, check the leakage at the connecting points. Check the leakage using a foaming agent or other measures and seal the leak with re-brazing, flare retightening or other methods. After sealing, execute an airtight test again.
Connected to indoor unit Main pipe Packed valve fully closed (gas side)
Header outdoor unit Service port
VL
VH Gauge manifold
Packed valve details
To gauge manifold Liquid-side service port Liquid-side valve Balance service port To outdoor unit Piping at site Balance valve Piping at site To outdoor unit To outdoor unit Gas-side valve
Brazed
Fully closed Service port
P
Gas-side service port Piping at site
Fully closed
Packed valve fully closed (liquid side)
Vacuum pump
Service port Packed valve fully closed (balance)
Follower units
· Use a vacuum pump with a high vacuuming degree [-100. 7kPa (5Torr, -755mmHg)] and large exhaust gas amount (40L/minute or larger). · Perform vacuuming for 2 or 3 hours, though the time differs depending on the pipe length. Check that all the packed valves at the liquid side, gas side, and balance pipe side are fully closed. · If the pressure does not reach -100. 7kPa or less, continue vacuuming for 1 hour or more. If the pressure does not reach -100. 7kPa after 3 hours of vacuuming, stop vacuuming and check for air leakage. · If the pressure reaches -100. 7kPa or less after vacuuming for 2 hours or more, close the valves VL and VH on the gauge manifold fully and stop the vacuum pump. [. . . ] · The unit does not perform test run for 3 minutes after turning the power on or stopping running.
7-segment display [A] [C ] [H ] [B] -C -H
[ [
] ]
Stop operation
1
Set the rotary switches on the interface P. C. board of the header unit back: SW01 to [1], SW02 to [1] and SW03 to [1].
7-segment display [A] [U1] [B] [ ]
EN
59-EN
30
60-EN
61-EN
31
SMMS-i Installation Manual SMMS-i Installation Manual
62-EN
11TROUBLESHOOTING
In addition to the CODE No. on the remote controller of an indoor unit, you can diagnose failure type of an outdoor unit by checking the 7-segment display on the interface P. C. Set every dip switch to OFF after checking.
Check code Indication on 7-segment display on the outdoor unit Auxiliary code F15 F16 F22
D600 D601 D602 D603 D604
Check code name Outdoor temp. [. . . ]